(Internal Building Storage)
___ Are all openings to rooms or other buildings provided with a 4-inch raised sill (or ramp) or the floor in the inside storage room at least four inches below the surrounding floor? 1910.106(d)(4)
___ Are all openings provided with approved self-closing fire doors? 1910.106(d)(4)
___ Is any wood used in the room at least 1 inch nominal thickness? (shelving, racks, etc.) 1910.106(d)(4)
___ Do storage rooms for flammable and combustible liquids have explosion proof lights? 1910.106(d)(4)(iii)
___ Do inside storage rooms have mechanical or gravity ventilation capable of 6 air exchanges per hour? 1910.106(d)(4)(iv)
___ Is the switch for the ventilation system located outside the storage room and does the same switch also control the lights? 1910.106(d)(4)(iv)
___ Is there at least one clear aisle maintained at least 3 feet wide? 1910.106(d)(4)(v)
___ Is it ensured that 30 gallon capacity or greater containers are not stacked upon one another? 1910.106(d)(4)(v)
___ Is dispensing done only by approved pump or self-closing faucet? 1910.106(d)(4)(v)
___ Are fire extinguishers of not less than 12-B units outside of, but located within ten feet of any inside storage area? 1910.106(d)(7)(i)(a)
___ Are "NO SMOKING" signs posted where combustible or flammable liquids are stored? 1910.106(d)(7)(iii)
___ Is an emergency drainage system provided to direct flammable and combustible liquid leakage and fire protection water to a safe location (equipped with trap or separator if connected to public system) 1910.106(e)(3)(iv)/(b)
(External Building Storage)
___ Is the external storage at least 20 feet from a building, or in lieu of, does the exposed blank wall have a fire-resistance rating of at least 2 hours?
___ Are appropriate fire extinguishers mounted within 75 feet of outside areas containing flammable liquids?
___ Are storage materials at least 3 feet below sprinklers or fire protection systems?
___ Is the storage area graded away from buildings or surrounded by a curb at least 6 inches high with provisions to drain rain water?
___ Are "NO SMOKING" signs posted where combustible or flammable liquids are stored?